DeVIce DATA OF THe 400 V DeVIceS

3.2.4 Power dissipation at rated operation

Device size
Rated switching frequency
Power dissipation at rated operation
Table 21:
Power dissipation of the 400 V devices
Rated operation corresponds to U
1)

3.2.5 Protection of the drive controller

Device
= 400V
U
N
size
gG (Iec)
Sccr 30 kA
21
125
22
160
23
200
24
250
Table 22:
Fusing of the 400 V / 480 V devices
P
/ W
1)
D
= 400 V; f
; I
N
SN
N
Max. size of the fuse / A
= 480V
U
N
class "J"
Sccr 10 kA
Sccr 30 kA
110
150
175
200
Short-circuit capacity
After requests from
DIN EN 60939-1
valid for the connection to a network: The devices are suitable for use in a
circuit capable of delivering not more than 30 kA eff. unaffected symmetrical
short-circuit current.
21
22
8
4
2
1356 1194 1320 1650 2074 1580 1887
; f
= 50 Hz (typically value)
N
= 480V
U
N
gr
125
SIBA 20 189 20.125
125
COOPER BUSSMANN 170M1368
125
LITTELFUSE L70QS125
160
SIBA 20 189 20.160
160
COOPER BUSSMANN 170M1369
175
LITTELFUSE L70QS175
180
SIBA 20 189 20.180
200
COOPER BUSSMANN 170M1370
200
LITTELFUSE L70QS200
200
SIBA 20 189 20.200
200
COOPER BUSSMANN 170M1370
200
LITTELFUSE L70QS200
and
EN 61800-5-1
23
24
4
8
2
4
Type
the following is