Mova Commissioning Detail; Start The Mova Applications; Communicating Locally Via Mova Comm - Siemens UTMC OTU Handbook

Table of Contents

Advertisement

This section expands on the steps in the commissioning checklist from the previous
section.
Step Section
1)
4
Check that the outstation has been installed correctly.
2)
-
Switch on the outstation's mains supply.
3)
5.3.1
Check that the System LED (LP1) is flashing.
4)
7.3.1

Start the MOVA applications.

7.3.1 Start the MOVA Applications
Connect to the outstation web server – see Appendix B for the PC setup required. On
the outstation web 'System' screen, click the 'Start' button for each MOVA stream which
is required. Note MOVA streams do not run by default.
Once a MOVA stream has been started, the MOVA application can be accessed via
MOVAComm.

7.3.2 Communicating Locally via MOVA Comm

5)
7.3.2
Use the appropriate MOVA Comm shortcut to connect to the
required MOVA stream.
Use this sequence when located at the outstation. If the PC connection has already
been established, the steps 1 and 2 can be skipped.
1. Connect the PC to the outstation front 25-way D-type handset connector.
2. From the Windows Start menu select "Start->Settings->Network Connections-
>Gemini Connection. If the PC has not been configured for direct IP
communications refer to Appendix B.
3. Select the shortcut for stream 1, 2, 3 or 4 as required to initiate MOVAComm. If
the shortcuts have not yet been set up, then complete the steps in Appendix B.5.
667/HB/31601/000

7.3 MOVA COMMISSIONING DETAIL

Action to be Performed
Page 80
UTMC OTU/MOVA Handbook
Issue 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Utmc mova

Table of Contents