HP 9000 Superdome Installation Manual page 51

Hide thumbs Also See for 9000 Superdome:
Table of Contents

Advertisement

a. Option 3 has been deleted.
b. A dedicated branch circuit is required for each PDCA installed.
c. Option 1 deleted January 2001.
d. 415 VAC phase-to-phase is possible.
e. Option 2 deleted January 2001.
f. Option 4 will be obsolete in the fourth quarter of 2001.
g. Refer to for detailed specifics related to this Option.
h. Option 5 will be obsolete in the fourth quarter of 2001.
Table 2-2
Option 4 through 7 Specifics
PDCA
Attached Power Cord
Part Number
A5201-69023
OLFLEX 190 (PN 600804) is a
(Option 6)
2.5 meter multi conductor,
600 volt, 90 degree C, UL and
CSA approved, oil resistant
flexible cable. (8 AWG 60 A
capacity)
A5201-69024
H07RN-F (OLFLEX PN
(Option 7)
1600130) is a 2.5 meter heavy
duty neoprene jacketed
harmonized European flexible
cable. (4 mm
A5201-69009
OLFLEX 190 (PN 600404) is a
(Option 4)
2.5 meter multi conductor,
600 volt, 90 degree C, UL and
CSA approved, oil resistant
flexible cable. (100 A capacity)
A5201-69008
H07RN-F (OLFLEX PN
(Option 5)
1600111) is a 2.5 meter heavy
duty neoprene jacketed
harmonized European flexible
cable. (63 A capacity)
Chapter 2
Attached Plug
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 532P6-14
(32A capacity)
2
32A capacity)
Mennekes
ME 4100P9
(100 A capacity)
Mennekes
ME 563P6-1235
(63 A capacity)
Unpacking and Inspecting
Unpacking the PDCA
Receptacle
Required
Mennekes
ME 460R9
(60 A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)
Connector
Provided
Mennekes
ME 4100C9
(100 A capacity)
Mennekes
ME 563C6-1245
(63 A capacity)
27

Advertisement

Table of Contents
loading

Table of Contents