5�22�- VOLTAGE ALARMS
In this point the phase-phase voltage thresholds above which the overvoltage alarm (
no voltage alarm (
Note: The alarm must be enabled (
Press the
digits to be modified.
In order to avoid possible false activations of said alarms, they have a predefined delay of 5 seconds.
The parameters to be configured are:
The value of the overvoltage alarm:
The value of the no voltage alarm:
When any of the two alarms are triggered, the device enters the Disconnection status and disconnects
all the stages. The device does not return to its normal operating status until the cause for the alarm
disappears.
The
key increases the digit value.
The
key reduces the digit value.
The
Press
Overvoltage alarm:
No voltage alarm:
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
96
E06
) should be triggered can be configured.
key to enter edit mode. It is identified by the
key skips to the previous digit and the
to validate the data; the
Maximum value: 99999 V
Minimum value: 0 V
Maximum value: 99999 V
Minimum value: 0 V
"5.21.- ENABLING ALARMS"
HI
�
LO
�
key skips to the next digit.
symbol disappears from the display.
Computer SMART III
).
symbol and the flashing of the
Instruction Manual
E05
) and the