4.2.3 Print Menu

The Print menu has options to print all rules,
via a standard Print window, or to create a
'.xls' file of the Control Matrix.

4.2.4 Thermal Alarm Verification Delay

If a Control Matrix Rule:
INPUT:
Alarm
OUTPUT: Remote fire output n
is used in conjunction with another Rule:
INPUT:
Thermal alarm
OUTPUT: Remote fire output n
then the remote fire output is operated after
the configured Day Mode delay unless the
alarm is thermal, in which case the remote
fire output is operated immediately.
However the thermal alarm remains subject
to a verification delay. The verification time
panel setting allows this delay to be adjusted
from its default (20 seconds) to give the
desired activation timing for the above Control
Matrix requirement.