Honeywell Notifier ID3000 Manual page 77

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

ID3000/ID2000 Fire Panel Configuration Tool Manual
A list of all 32 available sounder custom tones
is displayed, as shown at left. Check the
appropriate boxes adjacent to the listed tone.
While selecting tones the maximum of 8 is
exceeded a warning is displayed (see below
left) and the last device selected is ignored.
Select 'OK'. The selected custom tones are
now listed. In the example shown slot numbers
1, 2, 3, 5 and 7 have been used.
To delete a custom tone, highlight it in the list
and select 'Remove Custom Tone'.
Precedence Rules
Which slots are used are not important as the
panel ignores any unconfigured tone slots
when configuring Control Matrix output rules.
However, tone slot 'seniority' is considered if
two or more rules, all active, are configured
to activate in different modes. Tone slots
allocated to higher numbers have 'seniority'
or precedence over lower numbers.
To avoid situations occurring where there is a
conflict of sounder output modes, a set of
precedence rules are imposed. Refer to
Section 4.1.3 Output Event Statement for
further details on precedence rules.
3 - 22
997-291, Version 3.05
November 2010