Benelux Sprinkler Panel: Technical
Alarm contravenes EN54-2: 5.6, 6 by
lighting the zonal FIRE LED.
ID3000/ID2000 Fire Panel Configuration Tool Manual
10i
10v
10ii
OPAL
3 - 8
10 Other Functions (Select the required
device, then press the 'F2' or 'Enter' key
to display the Edit Device Data window,
which contains parameters applicable to
the sensor).
i
LED Operation (ID3000 only): select whether
the sensor's LEDs follow the panel setting
(Section 2.10) or are set to blink or not (non-
blink) or to always blink red (OPAL devices
only). If BLINK red is the global setting, there
is no 'Always Blink Green' option.
ii Priority Scan (CLIP protocol only): to scan
a sensor at intervals of less than one second,
select 'ON'. A maximum of 43 devices per
loop can be designated as priority. However,
to obtain a 1-second scan interval do not
designate more than 21 devices per loop as
priority (the scan rate becomes lower as more
devices are designated).
iii Remote LED follows panel state (OPAL
only): select if a sensor's remote LED is to
light under the control of the panel in alarm.
iv Technical Alarm (GAS Sensor: all modes.
Other sensors: Benelux Sprinkler Panel
only). If this option is selected, the
sounders do not operate. Instead, the
NON-FIRE ACTIVE LED illuminates on all
panels on the network. Relays and other
modules operate as in a fire condition.
ID3000: device is displayed on Tech. Alarm
tab instead of Fire tab.
v Lock Pre-alarm monitoring. If not
checked (default) and Time-of-Day (TOD)
is used to vary alarm sensitivity
(step 10[viii]), Pre-alarm sensitivity
changes with TOD by the same amount
997-291, Version 3.05
November 2010