ID3000/ID2000 Fire Panel Configuration Tool Manual
3
6
Panel
Repeater
4
5
No connection
6 - 12
Note: Control Matrix 'Fallback Input' Rules are
invoked automatically when there is a
communications loss with a fixed
number of panels; this number is not
user-configurable.
3 When all edits are complete for this station,
click on 'OK'.
4 If the system contains a large number of
AUX modules that may be logged at once,
there could be network delays if an alarm
occurs. To prevent this, several AUX 'logs'
can be reported in a single message by
setting a time delay. This option should
normally be left at 0. The available range
is 0 to 30 seconds in 1 second increments
(leading zeroes are required). If a delay is
necessary, it should be as low as possible
- consult NOTIFIER Technical Support.
5 In the Control Matrix input statement,
transfer flags are available from remote
panels only if this box is checked at the
remote panel(s) (may adversely load the
2
ID
net bandwidth and is not required for
many systems so default is unchecked).
6 When all edits are complete for the network,
click on 'OK'.
Note: To obtain a complete network, the
configuration file for each station must
be saved. If, during configuration editing,
two different unsaved stations are given
the same number, one station will be re-
numbered automatically and a message
will be displayed to confirm this.
997-291, Version 3.05
November 2010