ID3000/ID2000 Fire Panel Configuration Tool Manual
2
3
4
2 - 5
2 Use the spin buttons to set the Signal Degraded
Monitor Period in minutes. For each device,
the system counts the number of corrupted
responses within the time, and issues the
'Signal Degraded' fault message if the number
exceeds 1600. The longer the period, the
MORE sensitive the panel is to reporting such
faults. 0 = these faults are suppressed.
3 Use the spin buttons to set the Loops Start
Up BOOST period, which is used to ensure
the loops power up correctly when there are
many devices (greater than 16) between
isolators. Loop fault reporting is deferred
during this period.
4 The OPAL/Clip protocol checkbox of each
loop device may be toggled (display/hide)
using this checkbox. With WCT version
3.05, or later, this option is checked by
default, i.e. the loop devices' checkboxes
are shown.
Note: However, for WCT versions 3.03 and 3.04
OPAL protocol will be selected as the
default when installed on a PC with an
English-language operating system AND
the configuration tool language is English;
the OPAL 'switch' on the Loop Setting tab
is checked automatically. If neither of the
above conditions exists then the OPAL
switch is not checked. Also, when the tool
uploads a panel configuration which
contains at least one OPAL device, the
OPAL switch, again, is automatically
checked.
997-291, Version 3.05
November 2010