Honeywell Notifier ID3000 Manual page 118

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

ID3000/ID2000 Fire Panel Configuration Tool Manual
TOTAL NUMBER OF ZONES = 2040
MASTER
SLAVE
255
ZONES
MAXIMUM OF
7 SLAVE
PANELS
(255 ZONES
EACH)
SLAVE
255
ZONES
255
ZONES
REPEATER
REPEATER
6 - 3
Number of zones on network
There are two types of zone numbering available
on the Master/Slave network, available in both
Standard and VdS modes:
a. Local.
b. Network.
Local
The maximum number of zones on a network
is 2040, made up as follows:
a. One Master with 255 zones.
b. Up to 7 Slaves with 255 zones each.
The zones are numbered in the range 1 to 255
for each panel.
If zone indicator lamps are fitted, they only
indicate the status of that panel's zones.
Network
The maximum number of zones on a network
is 2040, made up as described for Local.
However, the zones are numbered in the range
1 to 8192 across the network. Each number
must be unique on the network. The panel has
an internal software table which maps the
network zone number to its internal zone
number (1 to 255).
If zone indicator lamps are fitted, they indicate
the status of the network zone numbers up to
a maximum of 256; higher numbers are NOT
indicated.
997-291, Version 3.05
November 2010