ID3000/ID2000 Fire Panel Configuration Tool Manual
1 - 16
Send Configuration to Panel
This allows you to load the configuration from
the PC to the panel:
1 Enter the panel's access level 3 passcode.
2 Click OK. The Send Configuration to Panel
window is displayed (but see note). If a
bitmap has been selected (Section 1.5.10),
check the top box to send it to the panel.
Check the bottom box to use the panel's
default logo, or neither box to use the panel's
current logo.
Note: With panel software version 4.30, or
later, if the configuration file contains
at least one OPAL protocol device and
the panel has one or more LIB PCBs
with software version prior to 14.01, the
user is warned that there is a LIB/loop
device incompatibility issue. Select
YES to continue, any OPAL devices will
be polled using CLIP protocol, or NO
to abort configuration download.
3 Select 'Send Data' (until this is done it is
possible to abort, via the Cancel Transaction
button, which becomes greyed when the data
transfer commences). With panel firmware
version 4.30, or later, before the configuration
data is transferred the firmware version is
momentarily displayed. Progress is shown
by the bar and by 'Transaction Status'
messages. When prompted at the panel,
press the panel's
button. When the data
transfer is complete, the Tool displays a
'Download Complete' message.
997-291, Version 3.05
November 2010