ID3000/ID2000 Fire Panel Configuration Tool Manual
i
iii
Immediate Release is for
use during
commissioning only and
must never be installed in
the manned room.
Extinguishing - if input event was alarm...
i
Select which of up to 32 Extinguishing
Systems the input applies to.
ii. Select the release mode for this entry
(modes are listed below).
Auto Release - will apply when the
sensors signal an alarm (Auto/Manual/
Off set to Auto).
Manual Release - will apply when the
Manual Release is operated (Auto/
Manual/Off set to either Auto or
Manual).
ii
Immediate Release - will apply when
the Immediate Release input is
operated (release is immediate and
overrides ABORT, OFF and HOLD -
see warning opposite).
For any of these, if 'Soak Timer' is selected,
the release will turn off after a delay
(configured in the panel settings for all
extinguishing systems), otherwise it will
operate indefinitely (until the panel is reset).
For Auto Release and Manual Release only,
if 'Over-ride' is selected, the release will
override the HOLD input (for use with HOLD
mode IRI, Section 4.1.4.4), otherwise the
HOLD input will override the release.
iii Set the (control) delay before the output is
activated (delay cannot be zero. Delay is
not applicable to 'Immediate Release').
4 - 32
997-291, Version 3.05
November 2010