Honeywell Notifier ID3000 Manual page 75

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

11ix
11xi
11
Benelux Sprinkler Panel: Technical
Alarm contravenes EN54-2: 5.6, 6
by lighting the zonal FIRE LED.
ID3000/ID2000 Fire Panel Configuration Tool Manual
11x
3 - 20
x Logged/Not Logged. For modules of type
AUX only, set individually as 'logged'
(recommended for fire-critical equipment)
or 'not-logged' (overridden by panel 'Log'
setting, see Section 2.10 for further
information).
xi Backup Alarm Monitor (MON modules on
ID
2
net only): If device is intended to relay
alarm status from a neighbouring panel to
provide backup if the ID
this option to ensure that alarms are treated
correctly by the panel. Do not include the
device in zone-specific or device-specific
Control Matrix rules. Backup Alarm Monitor
cannot be set at the same time as
Technical Alarm Input.
xii Technical Alarm (Benelux Sprinkler Panel
only). If this option is selected, the
sounders do not operate. Instead, the
NON-FIRE ACTIVE LED illuminates on all
panels on the network. Relays and other
modules operate as in a fire condition. Only
effective if 'Detect Fire' supervision is set
to ON. Not available for modules of types
BELL, CTRL and AUX. ID3000: device is
displayed on Tech. Alarm tab instead of
Fire tab.
11 To exit, click OK.
997-291, Version 3.05
2
net fails, select
November 2010