ID3000/ID2000 Fire Panel Configuration Tool Manual
4 - 7
OPAL Protocol Sounder Devices
Tool software version 3.01, or later, supports
advanced sounder devices with configurable
sounder tones. Only OPAL loop protocol supports
the configuration of these tones. When used on
CLIP protocol loops the enhanced protocol-
compatible sounders still function as described
above.
Each sounder output can be configured to use:
a. One of 32 distinct tone patterns
b. One of three volume settings (LOW,
MEDIUM or HIGH) configured using the
device's DIP swiches.
A system may be configured to use only 8 of
the 32 possible patterns offered.
These sounders are subject to precedence
rules. Refer to Section 4.3.2 Output Event for
details.
997-291, Version 3.05
November 2010