15: Print - Honeywell FIre-LITe ALArms MS-9600LS Manual

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Read Status
4.22.15 Print
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
Read Status Screen #5
DEVICE #
1D001
1D002
1D003
1D004
1D005
1D006
1D007
1D008
1D009
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
To print program data or control panel status, press 3 while viewing Read Status Screen #5. The
following screens will be displayed:
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
1=EXIT PRINTING
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on
page 160 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each address-
able smoke detector connected to the system. A printout, similar to the following example, will be
generated if an optional printer is connected to the FACP.
DEVICE TYPE
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
Chamber Value
The Chamber value should be within the indicated range for the following smoke detectors:
SD350(T), SD355(T), D350P(R), SD300(T), AD350 and AD355 Addressable Photoelectric
Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
CP350, CP355 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration
of 0.50%/ft. to 1.44%/ft.)
If the addressable smoke detector's Chamber reading is not within the acceptable range, clean the
detector and check the Chamber value again. If the reading is still not within the acceptable range,
immediately replace the detector.
PRINT
Print Screen #1
PRINT
Print Screen #2
%DRIFT COMP
CHAMBER
20
20
21
20
21
20
20
20
20
Operating Instructions
TIME/DATE
1281
12:01AM 01-08-2001
1281
12:01AM 01-08-2001
1259
12:01AM 01-08-2001
1309
12:02AM 01-08-2001
1281
12:02AM 01-08-2001
1322
12:02AM 01-08-2001
1280
12:02AM 01-08-2001
1215
12:02AM 01-08-2001
1310
12:02AM 01-08-2001
171