ID3000/ID2000 Fire Panel Configuration Tool Manual
11vi
11ix
vi SST. For CMX modules of type CTRL in
VdS mode only. This function disables the
module when the panel's SST AB/AN
pushbutton is operated.
vii Fire Control Device. For CMX modules
of type CTRL in VdS mode only. If this
function is selected, then the module is
disabled by the Brandfallsteuerung AB
pushbutton on the FBF. Enablements of
SST devices are blocked if they are held
disabled by Brandfallsteuerung AB, and
11vii
vice versa.
11viii
viii CDI-LMS. In VdS mode, CDI or ZMX
modules can be set to CDI-LMS. Activation
of the CDI-LMS input then results in
appropriate indications at the panel and FBF.
ix Open Circuit Indication Only. For
modules of types MON, MCP, SPRINKLER
and ASPIRATOR, intended for use in VdS
mode. If this function is selected, their open
circuit status is INDICATION (the
Technischer Alarm LED illuminates, non-
latching), otherwise it is defined as FAULT
(fault message displayed). In Standard
mode, the setting displays 'OPEN
CIRCUIT' instead of fault.
3 - 19
997-291, Version 3.05
November 2010