ID3000/ID2000 Fire Panel Configuration Tool Manual
4(i)
4(ii)
4(iii)
5
4 If the input event is Alarm, Specified
Individual Device, then instead of the zone
or cell selections the Select Individual
Device window is displayed. (i) Choose the
zone from the drop-down menu, (ii)
highlight the required device and then (iii)
click 'OK'.
5 If the input event is Alarm, Virtual Input
Point, then select the required Point from
those available in the Select Virtual Point
window and then click 'OK'.
Thermal Alarm
These options apply only to Optiplex and
SMART sensors. The input is active when a
sensor detects a thermal alarm (any normal
alarm rules configured for the active sensor
will also become active). The sensors can be
selected by zone (Any or specified) or by
individual device.
The option to set 2-devices coincidence is then
provided. Devices in alarm must be in the
same zone or cell, or in a range of cells if this
option is configured (refer to Section 2.12).
Multiple device coincidence is not available.
4 - 21
997-291, Version 3.05
November 2010