ID3000/ID2000 Fire Panel Configuration Tool Manual
4
5
6
7
4 Check the box if the disablement is to be
controlled by a time-of-day program, then
edit the times as described in Section 5.3.
Does not comply with EN54 - see
warning after step 5.
5 If the disablement is to end automatically
after a timeout, use the spin buttons to enter
the time period, range up to 1440 minutes
(24 hours). If there is a second disablement
during the time period, the timer is
restarted. Does not comply with EN54.
6 Set the required buzzer time interval during
disablement, range 2 to 120 minutes.
7 Set the sounder disablement access level.
Normally, to comply with EN54-2, level 2
should be selected (leave box unchecked).
Check the box to configure sounder
disablement at level 3.
2 - 16
EN54-2: 9.1.2
Disablement and re-
enablement MUST be a
manual operation at
Access level 2.
EN54-2: 9.1.2
Sounder disablement
must be at Access level 2.
997-291, Version 3.05
November 2010