Honeywell Notifier ID3000 Manual page 81

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

ID3000/ID2000 Fire Panel Configuration Tool Manual
Input
Device Co-incidence
Specified zone
Two sensors in alarm
on another panel in the specified zone
Any zone on
Two sensors in alarm
any panel
anywhere in the
network (including on
different panels)
Specific information for network
Outputs are applied only at the panel which
directly controls them (as stand-alone panels),
but inputs may be defined as originating at a
different panel. For example, to relate an output
operation on a device supervised by Slave 1
(on a Master/Slave network) to an input
originating at the Master, the Control Matrix
must be edited at Slave 1.
For network inputs, the definition 'Device Co-
incidence' depends upon the definition of the
input (see opposite).
4 - 4
997-291, Version 3.05
November 2010