Honeywell Notifier ID3000 Manual page 119

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

Note: The special case of a Stand Alone panel
(with or without repeaters) is configured
solely at the Specification Tab.
Slaves for which a panel name is displayed:
THESE NAMES ARE OVERWRITTEN if a
received Slave configuration has different (or
no) names. To retrieve the correct names, re-open
and save each of the Slave configurations.
3(iv)
3(i)
3(ii)
ID3000/ID2000 Fire Panel Configuration Tool Manual
1
2
F-NF30000
3(iii)
3(v)
ONLY
6 - 4
6.2.2 Procedure
To configure the panel for Master/Slave network
operation, do the following for the Master (the
Tool creates the data for Slaves automatically):
1 At the Specification Tab (Section 2.1)
configure the number of Slaves and repeaters
on the network.
2 Select 'Network Setup' on the System
Parameters menu. The Master-Slave
Network Setup window is displayed with a
tabular view of the Master and Slaves. To
view the repeaters, click on the '+' to the
left of the panel graphic (or click on '-' to
hide the repeaters). All repeaters are initially
shown below the Master (see step 5).
Slaves for which a panel has already been
configured are shown by their panel name,
others are just shown as 'Slave'.
3 The network configuration can be modified
in the Network Setup window (subject to the
limits given in Section 6.2.1). Use the
cursor to highlight one of the panels, then:
i
Insert Slave. A Slave panel is added at the
end of the table.
ii Insert Repeater. A Repeater is added at the
end of the list of Repeaters for the panel.
iii Delete the highlighted panel or repeater (the
'Delete' key on your PC also does this).
i v OK to save changes [or Cancel (v) to discard
them].
997-291, Version 3.05
November 2010