6.19.2 Calibration of analog output

 : Analog output signal selection
 : Inclination characteristic of analog output
 : Analog output bias
 Function
*
[Parameter setting]
 Analog output signal selection


6
Note 1: With 0 to 20mAdc (4 to 20mAdc) output, or 0 to 10Vdc output, set  to  or .
 Example of setting
Output signal from the FM terminal can be switched between 0 to 1mAdc output, 0 to 20mAdc output,
and 0 to 10Vdc output with the  setting. The standard setting is 0 to 1mAdc output.
Optional frequency meter: When using QS6T, set = (meter option (0 to 1mA) output).
Title
Function
Inclination characteristic of analog
output

Analog output bias

=1, =1, =0(%)
(mA)
20
0
0
Internal calculated value
=1, =0, =100(%)
(mA)
20
: Large gain
0
0
Internal calculated value
The analog output inclination can be adjusted using the parameter .
Adjustment range
0: Meter option (0 to 1mA)
1: Current (0 to 20mA) output
2: Voltage (0 to 10V) output
0: Negative inclination (downward slope)
1: Positive inclination (upward slope)
-1.0 - +100.0%
=1, =1, =20(%)
(mA)
20
4
f692
100%
=1, =0, =100(%)
(mA)
20
f692
4
100%
F-60
Default setting
0
100%
Internal calculated value
: Small gain
0
100%
Internal calculated value
E6582233
0
1
0