6.16 Setting motor constants

 : Auto-tuning
 : Slip frequency gain
 : Automatic torque boost value
 : Motor rated capacity
To use vector control, automatic torque boost and automatic energy saving, motor constant setting (motor tuning)
is required. The following three methods are available to set motor constants.
1)
Using the torque boost setting macro function () for setting the V/F control mode selection () and
auto-tuning () at the same time
2)
Setting V/F control mode selection () and auto-tuning () independently
3)
Combining the V/F control mode selection () and manual tuning
Caution:
If the settings for V/F control mode selections  are : automatic torque boost control, : vector control,
6
: energy saving.
Look at the motor's name plate and set the following parameters.
: Base frequency 1 (rated frequency)
: Base frequency voltage 1 (rated voltage)
: Motor rated capacity
: Motor rated current
: Motor rated speed
Set the other motor constants as necessary.
[Selection 1: Setting by parameter setting macro torque boost]
This is the easiest of the available methods. It conducts vector control and auto-tuning at the same time.
Be sure to set the motor for , , , ,  .
Set  to  (Automatic torque boost + auto-tuning)
Set  to  (Vector control + auto-tuning)
Set  to  (Energy-saving + auto-tuning)
Refer to section 5.4 for details of the setting method.
 : Motor rated current
 : Motor no-load current
 : Motor rated speed
 : Load inertia moment ratio
F-42