Toshiba TOSVERT VF-nC3E Instruction Manual page 238

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

[Alarm information]
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
Error code
N---
No detailed information

of past trip
NERR
No trip of past trip


OFF
ST terminal OFF
PASS/
Password verification
/
FAIL
result


RTRY
Retry in process

STOP
Deceleration stop
during power failure
function activated.
[Pre-alarm information]
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
The following error code and the frequency will flash alternately.
Error code
Name
C
Overcurrent pre-alarm
H
Overheat pre-alarm
L
Overload pre-alarm
P
Overvoltage pre-alarm

T
Communication pre-alarm
If two or more problems arise simultaneously, one of the following pre-alarms appears and blinks.
, , (The blinking alarms , , , h, t are displayed in this order from left to right.)
Problem
Possible causes
 The detailed information of past trip is
read by pushing the center of setting dial
during blinking nerr ⇔ number.
 No new record of past trip, after past trips
were clear.
 The ST-CC circuit is opened.
 After the password setting (f738), the
password was input to f739 (password
verification).
 The inverter is in process of retry.
 A momentary stop occurred.
The motor speed is being detected.
 The deceleration stop during power failure
with  is activated.
 When a current flows at or higher than the over current stall
prevention level.
 When the overheat protection pre-alarm level is reached.
 When the cumulative amount of overload reaches 50% or
more of the overload trip value.
 When the main circuit element temperature reaches the
overload pre-alarm level.
 When a voltage is generated at or higher than the over voltage
stall prevention level.
 When a voltage is generated at or higher than the over voltage
stall prevention level.
 Even if it was lower than the over voltage stall prevention level,
when a voltage is generated at sharp increse.
 When the communication was broken off at or higher than the
over parameter f803 setting.
L-5
 Normal operation.
To be returned by pressing MODE key.
 Normal operation.
 Close the ST-CC circuit.
 If the password is correct, pass is
displayed and if it is incorrect, fail is
displayed.
 The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
 To restart operation, power supply reset or
input an operation signal again.
Description
E6582233
Remedies
Remedies
Same as  (overcurrent)
Same as  (overheat)
Same as  (overload)
Same as  (overvoltage)
Same as err5 (communication
fault)
12