Setting Frequency Command Characteristics; Vi Input Point 1 Setting; Vi Input Point 1 Frequency - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

6.6.2
 : Analog/logic input selection (VI terminal)
 : VI Input point 1 setting
 : VI Input point 1 frequency
 : VI Input point 2 setting
 : VI Input point 2 frequency
 : Analog input filter
 Function
To fine adjust the frequency command characteristics for VI input, use the parameters f470 and f471 .
6
(Refer to section 6.6.4)
[Parameter setting]

 VI point 1 setting
 VI point 1 frequency
 VI point 2 setting
 VI point 2 frequency
 Analog input filter
Note 1: Do not set point 1 and 2 (  and  ) to the same value. If they are set to the same value,

Setting frequency command characteristics

Output frequency is adjusted in relation to frequency command according to external analog signals.
Analog signal is  set to 0: 0 to 10Vdc, 1: 4 to 20mAdc, 3: 0 to 5Vdc.
 analog input filter is effective for eliminating noise from frequency setting circuit. Increase if
operation cannot be done because noise effects stability.
Title
Function
Analog/logic input selection
(VI terminal)
 is displayed.
Adjustment range
0: Voltage signal input (0 - 10V)
1: Current signal input (4 - 20mA)
2: Logic input
3: Voltage signal input (0 - 5V)
0 - 100(%)
0.0 - 400.0 (Hz)
0 - 100(%)
0.0 - 400.0 (Hz)
4 - 1000 (ms)
F-12
E6582233
Default setting
0
0
0.0
100
50
64