Dc Braking; Dc Braking Starting Frequency; Dc Braking Current; Dc Braking Time - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

6.8

DC braking

 : DC braking starting frequency
 : DC braking current
 : DC braking time
 Function
A large braking torque can be obtained by applying a direct current to the motor. These parameters
set the direct current to be applied to the motor, the application time and the starting frequency.
[Parameter setting]
Title


DC braking starting frequency

DC braking current



DC braking time


Note1: During DC braking, the overload protection sensitivity of the inverter increases. The DC braking
current may be adjusted automatically to prevent tripping.
Note 2: During DC braking, the carrier frequency becomes the setting of parameter f300 (PWM carrier
frequency).
Note 3: DC breaking can be done by using terminal input. Input terminal 22: Assign DC braking command
(23 is reverse).
DC braking is applied while the terminal is ON, regardless of the  ,  settings. Even if
the terminal is OFF, DC braking is applied only for the  time.
The amount of DC braking depends on the  settings.
Function
Output frequency [Hz]
Set frequency
DC braking starting frequency

0
Output current [A]
0
Operation signal (F-CC)
F-19
Adjustment range
0.0-  (Hz)
0.0-100 (%) / (A)
0.0- 25.5 (s)
DC braking
Time [s]
DC braking current

DC braking time 
ON
OFF
E6582233
Default setting
0.0
50
1.0
6