YASKAWA SI-EM3D Installation Manual page 56

Ac drive option, modbus tcp/ip
Hide thumbs Also See for SI-EM3D:
Table of Contents

Advertisement

7 Modbus TCP/IP Messaging
Register Number
(Hex.)
bit F
0010 - 001A
Reserved
001B
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 (Hex.))
001C
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 (Hex.))
001D
Digital output option DO-A3 output value (binary)
001E - 001F
Reserved
No. (Modbus
Drive
Register)
Registers
2000
2001
56
Table 7.3 Drive Registers
Register Name
Drive Status
4B
(U1-12)
44
Motor Speed Monitor (U1-05)
Description
Terminal S8 input of broadcast message
Bit
0
1: During Run
1
1: During zero speed
2
1: During reverse
3
1: During reset signal input
4
1: During Speed Agree
5
1: Drive operation ready
6
1: Alarm
7
1: Fault
8
1: During Operation Error (oPExx)
1: Momentary power loss recovery
9
0: Power loss recovery
A
1: Motor 2 Selection
B
Reserved
C
Reserved
D
Reserved
E
ComRef status/ NetRef status
F
ComCtrl status/ NetCtrl status
YASKAWA TOEP C730600 0EA Modbus TCP/IP Installation Manual