YASKAWA SI-EM3D Installation Manual page 31

Ac drive option, modbus tcp/ip
Hide thumbs Also See for SI-EM3D:
Table of Contents

Advertisement

1.
Put the LED label (A) in the correct position on the drive front cover (B).
A - LED label
Figure 5.15 Put the LED Label on the Drive Front Cover
2.
Remove the keypad (E) and front cover (D).
Shut off power to the drive and wait for the time specified on the drive warning
label at a minimum. Make sure that the charge indicator LED is unlit, then remove
the keypad and front cover. Refer to the drive manuals for more information.
You can only install this option into the CN5-A connector on the drive control
board.
NOTICE
you observe correct electrostatic discharge (ESD) procedures. If you do not follow
procedures, it can cause ESD damage to the drive circuitry.
Note:
Remove the keypad, then move the keypad connector to the holder on the drive, then remove the front
cover.
YASKAWA TOEP C730600 0EA Modbus TCP/IP Installation Manual
B - Drive front cover
Damage to Equipment. When you touch the option, make sure that
5 Installation Procedure
31