Digital Inputs; Analogue Inputs - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Level 2
Duration
(GEN ON DURATION)
Load Transfer
(LOAD TRANSFER)
Table 6.8
Night Mode (NIGHT MODE)
Level 2
Night Mode
(NIGHT MODE RESTRICT)
Night Mode Start Time
(START TIME)
Night Mode Off Duration
(GEN OFF DURATION)

6.2.3 Digital inputs

Table 6.9
Digital Input # (DIG IN #)
Level 2
Source
(SOURCE)
Name
(NAME)
Polarity
(POLARITY)
Action
(ACTION)
Activation
(ACTIVATION)
Activation Delay
(ACTIVATION DELAY)

6.2.4 Analogue inputs

Table 6.10
Analogue Input 1 (LOP RES / DIG J)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
USER MANUAL 4189341227A UK
Range
00 hr 01 min. to 99 hr 59 min.
Enable
Disable
Range
Enable
Disable
00:00 to 23:59 hour
1 to 1440 min.
Range
See Digital input source selection in this document
Auxiliary Input #
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
0 to 180 s
Range
Not used
Digital Input J
Lube Oil Pressure
See Digital input source selection in this document
Auxiliary Input J
Page 25 of 86