Level 2
Over-current Threshold
(OVER CURR THRESHOLD)
Over-current Delay
(OVER CURR DELAY)
CT Correction Factor
CT Location
(CT LOCATION)
Table 6.25
Earth Leakage/Fan Current Monitoring (EARTH CURR MON)
Level 2
Current Monitoring
(FAN / EARTH MOMN)
Current CT Ratio
(CT RATIO)
High Current Action
(HIGH CURR ACTION)
High Current Threshold
(HIGH CURR THRESH)
Current Delay
(CURR DELAY)
Low Current Action
(LOW CURR ACTION)
Low Current Threshold
(LOW CURR THRESH)
Table 6.26
Load Monitoring (LOAD MONITOR)
Level 2
Generator Rating
(GEN RATING)
Overload Action
(OVERLOAD ACTION)
Overload Threshold
(OVERLOAD THRESHOLD)
Overload Monitoring Delay
(OVERLOAD MON DELAY)
Unbalanced Load Action
(UNBAL LOAD ACTION)
USER MANUAL 4189341227A UK
Range
5 to 10000 A
1 to 600 s
0.900 to 1.100
On Alt Output Cable
On Load Cable
Range
Earth Leakage Current
Fan Current
0 to 8000 / 5
None
Notification
Warning
Electrical Trip
Shutdown
0.1 to 10.0 A
5 to 60 s
None
Notification
Warning
Electrical Trip
Shutdown
0.1 to 9.9 A
Range
0 to 8000 kW
None
Notification
Warning
Electrical Trip
Shutdown
50 to 150 %
1 to 600 s
None
Warning
Electrical Trip
Shutdown
Page 35 of 86