Deif SGC 420 User Manual page 34

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Table 6.22
Voltage Monitoring (VOLT MONITOR)
Level 2
Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
Under-voltage Shutdown Threshold
(UV SHUTDOWN THRESH)
Under-voltage Warning
(UNDER VOLT WARNING)
Under-voltage Warning Threshold
(UV WARNING THRESHOLD)
Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
Over-voltage Shutdown Threshold
(OV SHUTDOWN THRESH)
Over-voltage Warning
(OVER VOLT WARNING)
Over-voltage Warning Threshold
(OV WARNING THRESHOLD)
Table 6.23
Frequency Monitoring (FREQ MONITOR)
Level 2
Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
Under-frequency Shutdown Threshold
(UF SHUTDOWN THRESH)
Under-frequency Warning Enable
(UNDER FREQ WARNING)
Under-frequency Warning Threshold
(UF WARNING THRESHOLD)
Over-frequency Shutdown Enable
(OVER FREQ SHUTDOWN)
Over-frequency Shutdown Threshold
(OF SHUTDOWN THRESH)
Over-frequency Warning Enable
(OVER FREQ WARNING)
Over-frequency Warning Threshold
(OF WARNING THRESHOLD)
Table 6.24
Current Monitoring (CURRENT MONITOR)
Level 2
CT Ratio
(LOAD CT RATIO)
Over-current Action
(OVER CURR ACTION)
USER MANUAL 4189341227A UK
Range
Enable
Disable
50 to 295 V phase-neutral
Enable
Disable
55 to 300 V phase-neutral
Enable
Disable
105 to 350 V phase-neutral
Enable
Disable
100 to 345 V phase-neutral
Range
Enable
Disable
10.0 to 59.0 Hz
Enable
Disable
11.0 to 60.0 Hz
Enable
Disable
26.0 to 75.0 Hz
Enable
Disable
25.0 to 74.0 Hz
Range
0 to 8000 / 5
None
Notification
Warning
Electrical Trip
Shutdown
Page 34 of 86