Deif SGC 420 User Manual page 31

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Table 6.16
S4 Sensor (AUX S4 CURR / DIG P)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(4-20 mA) Shutdown
(SHUTDOWN)
(4-20 mA) Shutdown Threshold
(SHUTDOWN THRESHOLD)
(4-20 mA) Warning
(WARNING)
(4-20 mA) Warning Threshold
(WARNING THRESHOLD)
(4-20 mA) Threshold Type
(THRESHOLD TYPE)
(4-20 mA) Circuit Fault Action
(OPEN CKT ALARM)
(4-20 mA) Calibration Table
(CURRENT)
(0-5 V) Shutdown
(SHUTDOWN)
(0-5 V) Shutdown Threshold
(SHUTDOWN THRESHOLD)
(0-5 V) Warning Threshold
(WARNING THRESHOLD)
(0-5 V) Threshold Type
(THRESHOLD TYPE)
(0-5 V) Circuit Fault Action
(OPEN CKT ALARM)
USER MANUAL 4189341227A UK
Range
Not used
Digital Input P
4 to 20 mA Sensor
0 to 5 V Sensor
See Digital input source selection in this document
Auxiliary Input P
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0.0 to 1000.0
Enable
Disable
0.0 to 1000.0
Greater Than Threshold
Less Than Threshold
None
Notification
Warning
Electrical Trip
Shutdown
Current: 4 to 20 mA
Value: 0 to 1000
Enable
Disable
0.0 to 1000.0
0.0 to 1000.0
Greater Than Threshold
Less Than Threshold
None
Notification
Page 31 of 86