Advertisement

Level 2
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(LOP) Circuit Fault Action
(OPEN CKT ALARM)
(LOP) Lube Oil Pressure Calibration Table
Table 6.11
Analogue Input 2 (FUEL LVL / DIG K)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(FLS) Low Fuel Level Shutdown
(SHUTDOWN)
(FLS) Shutdown Threshold
(SHUTDOWN THRESHOLD)
(FLS) Low Fuel Level Notification
(NOTIFICATION)
USER MANUAL 4189341227A UK
Range
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 1000 Ω
Pressure: 0.0 to 10.0 Bar
Range
Not used
Digital Input K
Fuel Level Sensor
See Digital input source selection in this document
Auxiliary Input K
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0 to 78 %
Enable
Disable