Deif SGC 420 User Manual page 29

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Table 6.14
S2 Sensor (AUX S2 RES / DIG N)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(S2) Shutdown
(SHUTDOWN)
(S2) Shutdown Threshold
(SHUTDOWN THRESHOLD)
(S2) Warning
(WARNING)
(S2) Warning Threshold
(WARNING THRESHOLD)
(S2) Threshold Type
(THRESHOLD TYPE)
(S2) Circuit Fault Action
(OPEN CKT ALARM)
(S2) Calibration Table
Table 6.15
S3 Sensor (AUX S3 CURR / DIG O)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
USER MANUAL 4189341227A UK
Range
Not used
Digital Input N
S2 Sensor
See Digital input source selection in this document
Auxiliary Input N
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0.0 to 1000.0
Enable
Disable
0.0 to 1000.0
Greater Than Threshold
Less Than Threshold
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 5000 Ω
Value: 0 to 1000
Range
Not used
Digital Input O
4 to 20 mA Sensor
0 to 5 V Sensor
See Digital input source selection in this document
Auxiliary Input O
Page 29 of 86