Incorrect or non-compatible tools

If non-compatible versions of fieldbus software tools are used, such as Standard Dictionary or
Device Description (DD) files, or if you are using the incorrect revision level of device firmware,
then device objects or some block objects may not be visible or identified by name. See the
following table for the possible causes and recommended actions.
Device and/or block objects not identified (Unknown).
Or
Parameters are not visible or identified by name.
Or
Honeywell-defined parameters are not visible.
Possible cause
Incorrect Standard
Dictionary, Device
Description (DD) or
Symbols on host
computer.
Incorrect pathnames to
descriptions on host
computer.
Incorrect version of
device firmware
Revision 4
Foundation Fieldbus RMA803 Remote Indicator User's Guide
Symptoms
Things to check
Verify that the Standard
Dictionary, the DD or symbols
files are correct for the device.
Check that the pathnames to
locations of the Standard
Dictionary, and DD files on the
host computer are correct.
Read the following Resource
block parameters:
DEV_REV (contains the
revision level of the resource
block).
DD_REV (contains the
device description of the
resource block).
Recommended action
Install the compatible version
of Standard Dictionary and
DD for the device on the host
computer.
Make sure that the
pathnames of the Standard
Dictionary and DD are in the
correct location for the
fieldbus software application.
Perform a code download of
the correct device firmware.
See Section Class 3.