5.9

Arithmetic block

The Arithmetic block is designed for using popular measurement math functions easily. The math
algorithm is selected by name and the type of function to be performed. The block is used for
calculating measurements from a combination of signals from the sensors. The block must not be
used in a control path. The block does not support process alarms.
The Arithmetic block supports the following functions:
Flow compensation, linear
Flow compensation, square root
Flow compensation, approximate
BTU flow
Traditional Multiply Divide
Average
Traditional Summer
Fourth order polynomial
Simple HTG compensated level
Fourth order Polynomial Based on PV

Execution

The block has five inputs, namely IN, IN_LO, IN_1, IN_2, and IN_3. The first two inputs (IN,
IN_LO) are designed for a range extension function that results in a Process Variable (PV), with the
status indicating the input in use.