Parameter List; Table 16: Diagnostic Transducer Block Parameters - Honeywell SmartLine RMA800 User Manual

Foundation fieldbus remote indicator
Table of Contents

Advertisement

Stress monitor
It is the amount of time the device has been used under stressful conditions. For example, say
temperature of the device. The stress monitor is based on the temperature of the device. The Stress
monitor is calculated in percentage.
Stress monitor = Amount of time the device was under stressful conditions

Parameter List

Parameter
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE
BLOCK_ERR
UPDATE_EVT
BLOCK_ALM
EL_TEMP_DIAGNOSTIC
POWER_TRAC
OP_VOLTAGE
TIME_IN_SERVICE
SERVICE_LIFE
STRESS_MONITOR
HON_RES_1
HON_RES_2
Page 46
Foundation Fieldbus RMA803 Remote Indicator User's Guide
-------------------------------------------------------------------------
Time in Service of the device

Table 16: Diagnostic Transducer block parameters

The revision level of the static data associated with the function
block.
The user description of the application of the block.
Used to identify grouping of blocks.
The identification number of the plant unit.
The actual, target, permitted, and normal modes of the block.
Reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that
multiple errors may be shown.
This alert is generated by any change to the static data.
The BLOCK_ALM is used for all configuration, hardware, and
connection failure or system problems in the block. The cause of
the alert is entered in the subcode field. The first alert to become
active sets the Active status in the Status attribute. As soon as the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if
the subcode has changed.
Electronic Temperature Diagnostic parameters.
Power Up Track Data.
Operating Voltage.
Summation of time in minutes that power has been applied to the
device since leaving the factory.
It is the elapsed Service life of device in percentage.
It monitors various diagnostic parameters which are then input
into an algorithm to calculate an estimated percent of time that the
Remote Indicator has spent in stressful conditions.
Reserved for Honeywell use only.