MSG
AGENCY
TYPE OF PROTECTION
CODE
Explosion proof:
Class I, Division 1, Groups A, B, C, D; T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T4
Class 1, Zone 1, AEx d IIC T4 Gb
Class 2, Zone 21, AEx tb IIIC T 95
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C,D, E,
FM
F, G; T4
A
Approvals
Class I Zone 0 AEx ia IIC T4 Ga
TM
(USA)
Non-Incendive
Class I, Division 2, Groups A, B, C, D; T4
Class I Zone 2 AEx nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Standards: FM 3600:2018;FM 3611: 2018; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1:
2015; FM 3610: 2018; ANSI/ UL 60079-11: 2014; FM 3810: 2018; ANSI/ UL 60079-15:
2013; ANSI/ UL 60079-31 : 2015; FM Class 3615: 2018; FM 3616: 2011
Explosion proof:
CSA 14.2689056
Class I, Division 1, Groups A, B, C, D;T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T4
Class I Zone 1 Ex db IIC T4 Gb
Ex db IIC T4 Gb
Zone 21 Ex tb IIIC T 95
Ex tb IIIC T 95
Intrinsically Safe:
B
CSA-Canada
CSA 14.2689056
Class I, II, III, Division 1, Groups A, B, C, D, E,
F, G; T4
Ex ia IIC T4 Ga
Non-Incendive
CSA 14.2689056
Class I, Division 2, Groups A, B, C, D; T4
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
Revision 4
Foundation Fieldbus RMA803 Remote Indicator User's Guide
Hazardous Locations Certifications
o
C Db
o
C Db
Electrical
Parameters
Note 1
o
C IP 66 Db
Note 2
Note 1
ALL
Note 1
Note 2
Note 1
ALL
Ambient
Temperature
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
-50
C to 70
C
º
º
-50
C to 85
C
º
º
ALL
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
-50
o
C to 70
o
C
-50
o
C to 85
o
C
ALL