Attributes

Supported
Modes
Alarm Types
Status
Handling
Page 68
Foundation Fieldbus RMA803 Remote Indicator User's Guide
The block supports the following modes:
AUTO (Automatic)
MAN (Manual)
OOS (Out of Service).
The block supports standard block alarms, (see section 5.2).
During normal operations, the value and status of the selected input
is shown by OUT. If the number of inputs with Good status is fewer
than MIN_GOOD, then the output status is Bad.
The SELECTED output status is Good (NC), until the block is out of
service.
The block supports two status option:
Uncertain as Good: If the selected input status is Uncertain, set
the OUT status as Good.
Uncertain, if in Manual mode: If the block is set to Manual
mode, the status of the Output is set to Uncertain.