Table 11: Advanced Displays With Pv Format Display Indications - Honeywell SmartLine RMA800 User Manual

Foundation fieldbus remote indicator
Table of Contents

Advertisement

Table 11: Advanced Displays with PV Format Display Indications

Display Indicator
Diagnostic /
Maintenance
These indicators are
displayed in the upper
left corner of the
screen when the
associated conditions
are present in the
Remote Indicator.
PV Value
PV Status:
Page 26
Foundation Fieldbus RMA803 Remote Indicator User's Guide
D
Diagnostic condition present
This indicator is displayed any time a diagnostic is present in the Remote
Indicator, either Critical or Non-Critical. If a Critical Diagnostic is present, the
message "Critical Diag" will flash at the top of the screen and the appropriate
Diagnostic screen will be inserted into the normal screen rotation.
To determine which Non-Critical diagnostics are active, use the local buttons to
call up the Non-Critical diagnostics menu (Main Menu\Diagnostics\Non-Critical).
Refer to Table 10 for details concerning the Non-Critical diagnostics.
M Maintenance Mode is active
This indicator is set by the Experion DCS. When this Mode is active, a screen
with the text "Available for Maintenance" will be inserted into the normal screen
rotation to make it easy to identify Remote Indicators that are available for
maintenance.
User Configurable. This field has 7 characters.
Maximum allowable numeric value of 9999999 or -999999.
If fractional decimals are configured, the fractional positions will be dropped as
required.
If the PV exceeds the values above limits, the PV is divided by 1000 and "K" is
appended to the result, allowing a maximum value with multiplier of 999999K or
-99999K
Good
The Remote Indicator is operating normally
Bad
The Remote Indicator has detected a fault condition.
The PV Status field will flash when this condition is present and the PV Value
will be displayed on a black background as shown below:
Unc
Uncertain (this status is only available for FF Remote Indicators)
The PV Value is outside of normal limits.
What It Means