<(C80) Initialize
>
*32
All parameters returns to ex-factory status. After initialization,
(not CAL) is effective. Perform "■Initial Adjustment" before using
positioner.
Procedure
1
Press the UP or DOWN button
(
) in calibration mode to
or
select Initialize (dFLt), and hold
down the set button (
1sec. or longer.
2
(not CAL) flash for confirmation. To
initialize, hold down the set button
+
(
) for 1sec. or longer. When
not initialized, hold down the mode
button (
) to return to previous
directly.
3
The LCD displays go (Go) for
confirmation.
To
down the set button (
1sec. or longer.
4
(not CAL) is indicated, and initialize
is completed.
32: This adjustment is available only after initial adjustment.
66
LCD display
+
) for
initialize,
hold
+
) for
No.IP8S-OM00009