SMC Networks IP8001 Series Operation Manual page 64

Smart positioner (lever type)
Hide thumbs Also See for IP8001 Series:
Table of Contents

Advertisement

(b00) Analog output setting
(C00) Calibration
<(C10) Check angle of
*22
feedback lever
>
<(C20) Simple balance current
*23
adjustment
>
*24
<(C30) Calibration
>
Possible to select analog output proportional output (inC) and
reversed output (dEC).
Procedure
Hold down the set button (
1
for
1sec.
or
parameter change mode.
2
Select proportional output (inC) or
reversed output (dEC) by UP or
DOWN button(
Hold down the mode button ( ) for
3
1sec. or longer to set output mode.
Mode button
Set button
≧1s
Proportional output
Possible to check the feedback lever angle, balance current
adjustment,
zero/span
parameter initialize.
The angle of the feedback lever unit connected to the valve stem is
checked.
22: For adjustment procedure, see "(2) Check the angle of the feedback
lever" of "■Initial Adjustment".
Adjust the balance current of the torque motor.
23: For adjustment procedure, see "(3)Simple balance current
adjustment" of "■Initial Adjustment".
Adjust zero-span and PID constant automatically.
24: For adjustment procedure, see "4.Calibration" of " ■ Initial
Adjustment".
63
)
longer
to
start
).
or
≧1s
Reversed output
Fig. 44
adjustment,
input
current
LCD display
or
adjustment,
No.IP8S-OM00009