If good (Good) is not displayed during or after adjustment
and the adjustment has not been completed successfully,
perform readjustment in the following manner.
<LCD displays high (HI) or low (Lo)
Procedure
When the LCD displays high (HI) or
1
low
(Lo),
rotate
adjusting screw until the LCD
displays good (Good)
2
Press and hold down the set button
(
) for 1sec. with good (Good)
indicated, and go back to step 3
(StP3) for readjustment.
3
If the LCD displays good (Good),
the
calibration
selection
automatically, and adjustment has
been completed.
11: 1 to 6 bars (-) are displayed to the side of high (HI) or low (Lo). The
number of bars tells how close the current adjustment is to good
(Good); Six bars is closest, and one bar is furthest. Rotate the
balance
adjusting
counterclockwise for low (Lo) until good (Good) displays. When the
balance adjusting screw is turned, bars (----) show up to check the
adjustment condition. Do not turn the balance adjusting screw until
the condition is decided.
12: If the actuator angle is outside of 50+/-2%, the LCD displays bars
(----). Do not rotate the balance adjusting screw until verification is
complete.
13: Bars (----) continue to display until verification is complete. If the
button is pressed before verification, the LDC displays a busy
message (bUSy).
24
*11
>
the
balance
*12 , *13
.
(CAL)
mode
screen
returns
screw
clockwise
for
LCD display
high
(HI)
and
No.IP8S-OM00009