End Stop Closed: Set - AUMA SQEx 05.2 Operation Instructions Manual

Part-turn actuators with actuator controls
Hide thumbs Also See for SQEx 05.2:
Table of Contents

Advertisement

Commissioning (basic settings)
Information
9.2.1.

End stop CLOSED: set

32
Exposed, rotating parts (discs/balls) at the valve!
Pinching and damage by valve or actuator.
End stops should be set by suitably qualified personnel only.
Never completely remove the setting screws [2] and [4] to avoid grease leakage.
Observe dimension T
The swing angle set in the factory is indicated on the name plate:
The setting sequence depends on the valve:
-
Recommendation for butterfly valves: Set end stop CLOSED first.
-
Recommendation for ball valves: Set end stop OPEN first.
Figure 25: End stop
[1]
Screw plug for end stop OPEN
[2]
Setting screw for end stop OPEN
[3]
Screw plug for end stop CLOSED
[4]
Setting screw for end stop CLOSED
Dimensions/sizes
05.2
T (for 90°)
17
T
11
min.
1.
Remove screw plug [3].
2.
Move valve to end position CLOSED with handwheel.
SQEx 05.2
SQEx 14.2 / SQREx 05.2
min.
07.2
10.2
17
20
11
12
SQREx 14.2
AMExC 01.1
12.2
14.2
23
23
13
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sqex 14.2Sqrex 05.2Sqrex 14.2Auma matic amexc 01.1

Table of Contents