Set End Stop Closed - AUMA PROFOX PF-Q80 Operation Instructions Manual

Part-turn actuators
Hide thumbs Also See for PROFOX PF-Q80:
Table of Contents

Advertisement

PF-Q80
PF-Q600
Modbus RTU
Information
7.1.1.

Set end stop CLOSED

The internal end stops limit the swing angle. They protect the valve in case of limit
switching failure during motor operation and serve the purpose as limitation for
manual operation via handwheel. They may not be used for torque tripping in end
positions during standard operation.
End stop setting is generally performed by the valve manufacturer prior to installing
the valve into the pipework.
Exposed, rotating parts (discs/balls) at the valve!
Pinching and damage by valve or actuator.
End stops should be set by suitably qualified personnel only.
Never completely remove the setting screws [2] and [4] to avoid grease leakage.
Observe dimension T
The swing angle set in the factory is indicated on the name plate:
The setting sequence depends on the valve:
-
Recommendation for butterfly valves: Set end stop CLOSED first.
-
Recommendation for ball valves: Set end stop OPEN first.
Figure 20: End stops
[1]
Screw plug for end stop OPEN
[2]
Setting screw for end stop OPEN
[3]
Screw plug for end stop CLOSED
[4]
Setting screw for end stop CLOSED
Dimensions/sizes
Q80
T (for 90°)
14.5
T
9
min.
With fitted handwheel: Dismantle handwheel prior to end stop CLOSED setting!
1.
Remove screw plug [3].
2.
Move valve to end position CLOSED with handwheel.
min.
Q150
Q300
14.5
18.5
9
11
Commissioning
Q600
18.5
11
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents