Automatic Motor Adaptation (Ama) - Danfoss VLT Decentral Drive FCD 302 Operating Manual

Hide thumbs Also See for VLT Decentral Drive FCD 302:
Table of Contents

Advertisement

VLT® Decentral Drive FCD 302
Operating Guide
13.7%
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
Illustration 23: Quick Menus
3.
Select language and press [OK].
4.
Enter the motor data in parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power [HP] through parameter 1-25 Motor
Nominal Speed. The information can be found on the motor nameplate. The entire quick menu is shown in International/
North American default parameter settings.
-
Parameter 1-20 Motor Power [kW]
-
Parameter 1-21 Motor Power [HP]
-
Parameter 1-22 Motor Voltage
-
Parameter 1-23 Motor Frequency
-
Parameter 1-24 Motor Current
-
Parameter 1-25 Motor Nominal Speed
0.0 Hz
Motor Setup
1 - 21 Motor Power [kW]
2.2
kW
Illustration 24: Motor Set-up
5.
Continue set-up of Quick Menu parameters:
a.
Parameter 5-12 Terminal 27 Digital Input. If terminal default is [2] Coast inverse, it is possible to change this setting to
[0] No operation.
b.
Parameter 1-29 Automatic Motor Adaptation (AMA). Set desired AMA function. Enable complete AMA is recommen-
ded.
c.
Parameter 3-02 Minimum Reference. Set the minimum speed of the motor shaft.
d.
Parameter 3-03 Maximum Reference. Set the maximum speed of the motor shaft.
e.
Parameter 3-41 Ramp 1 Ramp Up Time. Set the ramping up time regarding synchronous motor speed, ns.
f.
Parameter 3-42 Ramp 1 Ramp Down Time. Set the ramping down time regarding synchronous motor speed, ns.
g.
Parameter 3-13 Reference Site. Set the site from where the reference must work.

5.5 Automatic Motor Adaptation (AMA)

AMA is not relevant for permanent magnet motors.