VLT® Decentral Drive FCD 302
Operating Guide
Illustration 6: Allowed Mounting Positions - Hygienic Applications
3.3.3.1 Mounting the Installation Box
ELECTRICAL HAZARD
Applying power to the unit at this stage could result in death or serious injury.
-
Do not apply power before the electrical installation is complete.
PERSONAL INJURY OR PROPERTY DAMAGE
Do not switch on the mains before the 4 screws are tightened. Failure to tighten these screws can result in personal injury or
material damage when the unit is loaded.
-
Tighten screws before switching on power.
-
Ensure that the strength of the mounting location can support the unit weight.
•
Use the holes on the rear of the installation box to fix mounting brackets.
•
Use proper mounting screws or bolts.
•
For hygienic versions, use cable glands designed to meet hygienic application requirements, for example Rittal HD
2410.110/120/130.
1.
Mount the VLT® Decentral Drive FCD 302 vertically on a wall or machine frame. For hygienic versions ensure that liquids
drain off the enclosure and orient the unit so the cable glands are located at the base.
16 | Danfoss A/S © | 2020.07
W A R N I N G
W A R N I N G
Mechanical Installation
AQ267036816112EN-000101 / 130R0208