6.8 List of Warnings and Alarms
The following warning and alarm information defines each warning or alarm condition, provides the probable cause for the condi-
tion, and entails a remedy or troubleshooting procedure.
6.8.1 WARNING/ALARM 4, Mains Phase Loss
Cause
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input
rectifier. Options are programmed in parameter 14-12 Function at Mains Imbalance.
Troubleshooting
•
Check the supply voltage and supply currents to the drive.
6.8.2 WARNING 5, DC Link Voltage High
Cause
The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
6.8.3 WARNING 6, DC Link Voltage Low
Cause
The DC-link voltage (DC) is lower than the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still
active.
6.8.4 WARNING/ALARM 8, DC Undervoltage
Cause
If the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply
is connected, the drive trips after a fixed time delay. The time delay varies with unit size.
Troubleshooting
•
Check that the supply voltage matches the drive voltage.
•
Perform an input voltage test.
•
Perform a soft-charge circuit test.