VLT® Decentral Drive FCD 302
Operating Guide
6 Maintenance, Diagnostics and Troubleshooting
6.1 Maintenance and Service
Under normal operating conditions and load profiles, the drive is maintenance-free throughout its designed lifetime. To prevent
breakdown, danger, and damage, examine the drive for loose terminal connections, excessive dust buildup, and so on, at regular
intervals. Replace worn or damaged parts with Danfoss authorized parts. For service and support, contact the local Danfoss suppli-
er.
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death,
serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command,
an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condi-
tion.
-
Press [Off] on the LCP before programming parameters.
-
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor
start.
-
Check that the drive, motor, and any driven equipment are in operational readiness.
6.2 Cleaning
The enclosure (IP66/NEMA type 4x indoor) provides protection against dirt and water ingress. The enclosure is suitable for cleaning
methods and solvents used in food and beverage plants. Use the solvent concentration recommended by the manufacturer. Avoid
high-pressure hot water cleaning at close proximity or of long duration, because this method of cleaning can damage gaskets and
labels.
6.3 Frontal LEDs
The actual status can be read via 6 LEDs, which signal the actual status of the unit.
ON
W ar ning
A lar m
Bus MS
NS1
NS2
Illustration 25: Frontal LEDs
Table 16: Description of Frontal LEDs
Name
Color
ON
Green
Warning
Yellow
Alarm
Red
Bus MS
Only relevant if optional fieldbus is present. See fieldbus-dedicated manuals for
specific information.
Bus NS1
Only relevant if optional fieldbus is present. See fieldbus-dedicated manuals for
specific information.
Danfoss A/S © | 2020.07
W A R N I N G
Status
On
Off
On
Off
Flashing
Off
Maintenance, Diagnostics and
Troubleshooting
Indication, frontal LEDs
The drive receives power from
mains voltage or external 24 V
supply.
No power from mains voltage or
external 24 V supply.
Warning situation is present.
No warning is present.
Alarm is present.
No alarm is present
Bus Module Status
Bus Network Status 1
AQ267036816112EN-000101 / 130R0208 | 41