4.7.2 Connecting Several Motors

The drive can control several parallel-connected motors. The total current consumption of the motors must not exceed the rated
output current I
for the drive.
M,N
Installations with cables connected in a common joint are only recommended for short cable lengths (maximum 10 m (38.2 ft)).
When motors are connected in parallel, parameter 1-29 Automatic Motor Adaptation (AMA) cannot be used.
The electronic thermal relay (ETR) of the drive cannot be used as motor protection for the individual motor in systems with paral-
lel-connected motors. Provide further motor protection by thermistors in each motor or individual thermal relays. Circuit breakers
are not suitable as protection.