5.12.2 Monitor display selection of the operation panel
(Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564)
The monitor to be displayed on the main screen of the operation panel can be selected.
Parameter
Name
Number
DU/PU main display data
52
∗1
selection
170
Watt-hour meter clear
171
Operation hour meter clear
Monitor decimal digits
268
∗1
selection
Energization time carrying-
563
over times
Operating time carrying-
564
over times
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗1
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
∗2
The setting values "56 and 57" are for manufacturer setting. Do not set.
(1)
Monitored item description list (Pr. 52)
Set the monitored item to be displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) in Pr. 52 DU/PU
main display data selection.
Refer to the following table and set the monitored item to be displayed.
Monitored Item
Output frequency
Output current
Output voltage
Fault display
Frequency setting value
Motor torque
Converter output voltage
Regenerative brake duty
Electronic thermal relay
function load factor
Output current peak value
Converter output voltage
peak value
Output power
Cumulative energization time
∗1
Actual operation time ∗1, ∗2
Motor load factor
Initial Value
0
(output
frequency)
9999
9999
9999
0
0
Unit
Pr. 52 Setting
0.01Hz
0/100
Displays the inverter output frequency.
0.01A
0/100
Displays the inverter output current effective value.
0.1V
0/100
Displays the inverter output voltage.
0/100
Displays 8 past faults individually.
0.01Hz
5
Displays the set frequency.
Displays the motor torque in % on the assumption that the rated motor torque
0.1%
7
is 100%. (Displays 0% during V/F control)
0.1V
8
Displays the DC bus voltage value.
0.1%
9
Brake duty set in Pr. 30, Pr. 70
Displays the thermal cumulative value on the assumption that the thermal
0.1%
10
operation level is 100% (Larger thermal between the motor thermal and
transistor thermal). ∗4
Holds and displays the peak value of the output power monitor.
0.01A
11
(Cleared at every start)
Holds and displays the peak value of the DC bus voltage value.
0.1V
12
(Cleared at every start)
0.01kW
14
Displays the power on the inverter output side
Adds up and displays the energization time after inverter shipment.
1h
20
You can check the numbers of the monitor value exceeded 65535h with Pr. 563.
Adds up and displays the inverter operation time.
1h
23
You can check the numbers of the monitor value exceeded 65535h with Pr. 564.
Can be cleared by Pr. 171. (Refer to page 149)
Displays the output current value on the assumption that the inverter rated
0.1%
24
current value is 100%.
Monitor value = output power monitor value/rated inverter current 100 [%]
Monitor display and monitor output signal
Setting Range
Select the monitor to be displayed on the
0, 5, 7 to 12, 14, 20,
operation panel.
23 to 25, 55, 61, 62,
Refer to the following table for monitor
∗2
100
description.
0
Set "0" to clear the watt-hour meter monitor.
Set the maximum value for the monitoring from
10
communication to 9999kWh.
Set the maximum value for the monitoring from
9999
communication to 65535kWh.
Set "0" in the parameter to clear the operation
0, 9999
time monitor.
Setting 9999 does not clear.
0
Displayed as integral value
1
Displayed in 0.1 increments.
9999
No function
The numbers of cumulative energization time
0 to 65535
monitor exceeded 65535h is displayed.
(reading only)
(Reading only)
0 to 65535
The numbers of operation time monitor
(reading only)
exceeded 65535h is displayed. (Reading only)
Description
Description
147